AD14 Series
Evaporative cooling: a completely natural way for refreshing air
LITERATURE
RELATED LINKS
| Temperature (°C) | Relative humidity | ||||||
| 20% | 30% |
40% | 50% | 60% | 70% | 80% | |
| 20 | 10.2 | 11.6 | 13.1 | 14.3 | 15.6 | 16.8 | 17.9 |
| 25 | 13.7 | 15.4 | 17.0 | 18.6 | 20.0 | 21.3 | 22.6 |
| 30 | 17.0 | 19.1 | 21.0 | 22.8 | 24.4 | 26.0 | 27.4 |
| 35 | 20.4 | 22.9 | 25.1 | 27.1 | 29.0 | 30.6 | 32.1 |
| Treated air flow | m3/h | 14,000 | |
| Delivery channel attachment (lower outlet) | mm | 645 x 645 | |
| Electric power | axial fan | kW | 1.5 |
| circulation pump | kW | 0.05 | |
| Weight | empty | kg | 55 |
| in operating conditions | kg | 92 | |
Due to continuous product innovation and development, Robur reserves the right to change product specifications without prior notice.